Abstract
|
Article Information:
Study on Power Supply System by Using CT in High-Voltage Transmission Lines
He Zhi-Min, Yue Tian-Chen, Liu Ya-Dong, Sheng Ge-Hao, Jiang Xiu-Chen, Zhang Ying-Bin, Li Shu-Qin and Wang Qiang
Corresponding Author: He Zhi-Min
Submitted: January 19, 2013
Accepted: March 21, 2013
Published: November 10, 2013 |
Abstract:
|
In online monitoring of the transmission line, its power supply is one of the key issues. This study presents a device using special transformer which can induce power to supply the high side circuitry. The front-end of the protection device includes output-power-control circuitry, which can take output-power limited to a small range. At the back side it contains rechargeable lithium batteries. By using the reasonable control strategy, it can provide a stable output-power at the transmission line current ranging from 40 to 1500A. And in the larger current the fever of transformer is not serious. Experiments show that the power supply system has the high reliability and efficiency.
Key words: Output with stable voltage, power supply of CT, power control, transmission line, , ,
|
Abstract
|
PDF
|
HTML |
|
Cite this Reference:
He Zhi-Min, Yue Tian-Chen, Liu Ya-Dong, Sheng Ge-Hao, Jiang Xiu-Chen, Zhang Ying-Bin, Li Shu-Qin and Wang Qiang, . Study on Power Supply System by Using CT in High-Voltage Transmission Lines. Research Journal of Applied Sciences, Engineering and Technology, (20): 3859-3864.
|
|
|
|
|
ISSN (Online): 2040-7467
ISSN (Print): 2040-7459 |
|
Information |
|
|
|